GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

glowworm betacom boiler, pressure too high?

i have a glowworm betacom 30c boiler and the pressure is too high. it went too low and i filler it via the filler valve. thought i was being careful but the pressure then went up to 3 bar. having read some forums i have tried bleeding a radiator(the towel rail in the downstairs bathroom was the nearest). this seems to have made the problem worse and the pressure is now at 3.5 bar, heating on or off. can anyone give me sime advice o what to do?
lucy, May 2010
thank you Nik, the boiler is now at a good pressure and i found the fault where the water was coming in. Top tips!!

lucy, May 2010
You may need to take a large amount of water out of the system. Too make sure that the Filler valve (mains top up) is fully shut ( it may be letting by due to faulty valve seat or dirt) you may need to issolate the mains comming into your property. There may be a valve before the filler loop that you could issolate.
You then need to switch off all power to your boiler/heating system. Drain the system from a suitable point. Should be a fitting either on a radiator pipework or near the boiler. If not issolate a small radiator ( both sides off the Radiator valves). There will be water in it so open the air vent and slowly drain it first be lossening a radiator fitting, you can carefully drain the radiator. When empty , tighten the fitting and open up valves again. This may be enough water to drop pressure down to around 1.5 Bar. If not repeat draining procedure. If you feel confident you could remove the radiator completely and use one of the valves to drain the system quicker. Kepping an eye on the pressure gauge at all times. When you have reached ideally 1.5Bar reopen the propery mains valve and any other valves one by one and see if the pressure remains constant.

Nik, May 2010