Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

my glow worm 24cxi shows f13 what is the prob no loose conections?

my boiler is showing f 13 no loose conections what is the prob and is it a comon fault
andy, July 2010
got the same problem at the present time after fitting new power interface and new pcb main board,boiler works fine but then keeps shutting down with f13 code,re starts as soon as i switch the reset switch and again runs fine until the intermitant fault re-occurs checked every wire and connection block to main board till i,m sick of doing it.Getting fed up of re-setting boiler every half hour.keep paying tech guys just to be told what i already know,theres a bad connection somewhere.

Peter, January 2012
Had this problem with mine a few times.... the on/off switch contacts are burnt. Remove the front panel, lower the front of switch panel, behind the on/off knob is a crappy little slide switch. Make a note of the wiring connections, disconnect and remove the switch. With a very small screwdriver/sewing needle, carefully dismantle the switch and clean the contacts inside. reassemble, refit, and all will be ok. F1 codes started coming up too for the same reason...

barry, December 2010
You are not alone I have the same problem too.

Shal, August 2010
Hi Did you find out what the problem was as I have the same problem?

Roy, July 2010