andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

worcester heatslave 15/19?

my heatslave 15/19 is playing up its serviced every year and the boiler man said its a good boiler, anyway i now have no heating, the boiler fires up but the radiator dont get hot, hot water not a problem. can anyone help thanks
phil, September 2010
things to check
the dial on the front of the boiler is there a click as you turn it
if not replace it
is there 240 on the room stat going onto the pcb it is marked, top middle of the board if not your timer or room stat has gone
when you turn the heating dial on the front of the boiler does relay RL3 activate possible pcb.
and lastly is there 240 to black cable on diverter valve if yes then diverter valve has gone or brass wear seized

plumbbob, December 2010
Had exactly the same problem, with the same boiler, diverter valve was stuck on mine.

handyandy, November 2010
Same problem, if you find out let me know. I'll do likewise.

Not Hot Hank, October 2010
link Click here to see other fixes for Worcester 15/19.