Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Ferroli Modena 80E Losing pressure?

Hi, please can you advise? When the CH is used the pressure gradually reduces over a period of a couple of days, and then the system wont run. I have replaced the relief valve which was definitely faulty, and now the pressure holds up for much longer now - a couple of weeks. Is the expansion tank likely to be faulty? What pressure should it be charged to?
Norman John, July 2006
how do u set the pressure to 1 bar

LEE REILLY, November 2006
the exspansion vessel is usually charged to about 1bar.......... isolate flow and return valves on boiler drain through relief valve to take pressure off exspansion vessle when drained you can attach a foot pump with suitable gauge and re set pressure

baldy02920, October 2006