andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

greenstar Ri boiler green light flashing ?

heating not working I reset thermostat boiler started up red light came on main switch then after a few minutes boiler stopped.
george blake, December 2010
According the user manual - "CONDENSATE DRAIN
This is a condensing boiler and the
terminal will, at times give out a plume of
water vapour. This is quite normal.
The boiler also produces quantities of
condensate which is discharged regularly
by a syphon within the boiler via a pipe to
drain. This pipe must not be blocked or
altered in any way." Is your pipe insulated ? If not, the water may be frozen during the cold weather in the last few weeks ? Try to de-ice with the hairdryer and/or warm water . Make sure you use the circuit breaker when you use the hairdryer and remember water and electricity do not go well together ! Good luck

Peter_Charlie, December 2010