Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Glow worm compact 100e, leaking water on prv?

I have the above mentioned boiler and over the past week has started leaking water out the prv (pressure relief valve). When the boiler is cold i fill it up to just over 1bar then when the heating starts up all is fine until the pressure reads about 2.8bar then it starts to drip out the prv until it reads about 2bar. Then when the heating is off and gone stone cold again it only reads 0.3 bar. Why is my boiler releasing the water? Thanks.
Also check out my other problem titled
"glow worm compact 100e warm (not hot) water."
Billybob, December 2010
Cheers carefree,
Will look into that :)
Billybob

Billybob, December 2010
Re-pressure the expansion vessel

Carefree, December 2010