andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

water overheating on my ferroli 77ff combi?

my pressure gauge keeps overheating making the radiators and tap water far to hot, i have to keep topping it up as the safety valve blows off at 3 bars. could it be the overheat cut off thermostat
bill, February 2011
the pressure gauge can't overheat or cause water to be too hot when the system is cold the pressure should be 1-1.5 bar if when the boiler comes on it rises very quickly over 3 bar then you've a problem with the pressure vessel before you do some serious damage suggest you go to ferolli website view your boiler manual it explains how the boiler works

brian, February 2011
hi, unlikely stat fault as it has 2 stats, possibly expansion vessel lost charge pressure ( 1.5 bar ) or it needs replacement.

peter, February 2011