narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

Galaxy 16+ factory default?

I'm trying to default a galaxy 16+ I seem to recall there was a process of linking out a zone on power up or something like that but it was many years ago when I last did it. Anyone know how to do it?
TomTv, April 2011
I had the flashing light problem on the keypad (change fuse or battery).

Thank you Acorn for the engineer/manager codes.

Just replaced battery (from Screwfix) on my ADT alarm and, when it asked to call ADT with code 50887, I input the engineer code and it cleared the error.

Sheila, March 2017
Any know if you can do the same thing on a 520 ??

Dickyboy, September 2016
Many Thanks Acorn for your help. Its nearly 10yrs since I last had to work on a 16+. Unfortunately I dont work for ADT as they were the main users for the panel but from one alarm engineer (for over 10 yrs) to another I appreciate the help

TomTv, April 2011
dream on,

gts, April 2011
Anyone can post what they wish, I just thought giving defaulting info was not a thing professionals did.
Yes you can trawl the web for some items, but the better equipment isnt so easy...............for a reason.

Alarm, April 2011
I think I must have been having a brain storm or something.

ac, April 2011
and before you say that you dont get manual with galaxy panels,i know,but,u can buy it

gts, April 2011
alarm guy,acorn knows as well as i do,that alarm panels are bought by crimminals as well as prof guys,they can read,believe it or not,and with those panels,what do they get?an engineering manual,so,he aint giving anything away,welcome to the real world

gts, April 2011
So now defaulting is given out?

Since when?

Alarm, April 2011
GALAXY 16 & 16+
ENGINEER = 1122
MGR = 1234
Defaulting
To default Engineer code = short zone 1. Down power then restart.
Input Default code 1122 and then remove short.
Default Mgr code = Engineer mode option 6 Parameters, 6 User options, then 10 Reset MGR.

HOLDS all zones and parameters.

acorn, April 2011