andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

how can I fix my Vailant ecoTEC plus 831 boiler?

My eco TEC 831 is unable to maintain the pressure at 2 bars, it is 1 bar over and going into the red zone. Any solution please.
AL, December 2011
The pressure vessel wants checking.. Pressure should be 0.75 bar empty not 2 bar !!!!

Steve, December 2011
Pressure vessel need recharge with cycle pump To 2bar with system drain out also look that by pass not blocked and pump need clean up

ltd, December 2011