Jon asked ... How do I remove the flywheel. Mountfield 1640h ride on mower?    |    Keith Mumby asked ... Fordson starter solenoid?    |    Suzanne asked ... Washing programme stops after 3 minutes?    |    Rif asked ... Kenwood Dishwasher KID60S20 leaking from front?    |    Fraser asked ... Spares for power craft ppcs 38cc?    |    Click here to ask your question

pressure on system running hgher than normal?

system set for 2 bar but when running goes to 3.5 bar what is the problem

Thanks
jim bradhsaw, February 2012
YEP.
should be 1 bar cold, and why isnt the system pressure venting?? the pressure relief valve should operate with a banging sound at 3 bar.....
if its still hitting 3+bar when youve dropped the COLD pressure to 1 bar, then as said, the expansion vessel is ruptured and needs renewal, or a cheaper option, fit an external 18litre vessel on the return pipework to the boiler and leave the faulty vessel where it is.
yes, this IS allowed!!

Mark properjob, February 2012
dump some water out of system to 2bar hot or 1bar cold can have a difference of 1bar hot or cold also check air pressure in your exspansion tank could be low should be 10lbs ish if its got water in the the air side its had it

kevin the boiler man, February 2012