andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

my vaillan ecotech boiler pressure is at the max on the red side?

I have a vaillant ecotech boiler. The pressure was down so I tried to raise it but forgot to switch the pressure off. It was on all night. It's now leaking and shows on the screen where you normally see the temperature 23c and 2.3 bar. Is this a serious fault and was has gone wrong?

Thanks
Sadie, March 2012
thats ok ,first why did it drop they must be leak in system,repair that first,normal working pressure is 1.2bar can go up to 2.5 boiler will work fine,you can bring it down by taking water from radiator air vent

ltd, March 2012