GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

24i junior problem?

boiler hung and fitted all connections good filled and vented system and boiler .no external controls. therefore a link between the lr and ls was made .fired boiler .ok hot water perfect.but no h.deselected hw. ran ch only boiler fired but,no water circulated the tops of the flow got hot but didnt move.cchecked valves ,they were open.boiler ran for 20/ 30 secondsthenstopped.green flame indicator went out.no lockout light ,nor any flashing lights. boiler blue unaltered.fault guide suggested programmer,but that works otherwise it wouldnt start.the control panel,but again the thing does start but only for 20/30 second period. to me it seems that the diverter valvemay be the problem.how with out removing this can i determine if i am correct?
jonsey01, April 2012
you can remove actuator head on divertor valve without draining down boiler & check the pin moves in & out for CH & DHW
if it doesnt actuator faulty
if it does then external system fault
are there any isolation valves on the CH pipes [apart from boiler valves]
something has to be stopping the water circulating around the system
if not even 1 rad is heating up then the problem must be between boiler & 1st rad

manwithnoname, April 2012