andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

24i junior problem?

boiler hung and fitted all connections good filled and vented system and boiler .no external controls. therefore a link between the lr and ls was made .fired boiler .ok hot water perfect.but no h.deselected hw. ran ch only boiler fired but,no water circulated the tops of the flow got hot but didnt move.cchecked valves ,they were open.boiler ran for 20/ 30 secondsthenstopped.green flame indicator went out.no lockout light ,nor any flashing lights. boiler blue unaltered.fault guide suggested programmer,but that works otherwise it wouldnt start.the control panel,but again the thing does start but only for 20/30 second period. to me it seems that the diverter valvemay be the problem.how with out removing this can i determine if i am correct?
jonsey01, April 2012
you can remove actuator head on divertor valve without draining down boiler & check the pin moves in & out for CH & DHW
if it doesnt actuator faulty
if it does then external system fault
are there any isolation valves on the CH pipes [apart from boiler valves]
something has to be stopping the water circulating around the system
if not even 1 rad is heating up then the problem must be between boiler & 1st rad

manwithnoname, April 2012