3 hours ago andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Click here to ask your question

how do i add pressure on my f30 boiler?

I bled my upstairs radiators as they were only hot at the bottom. now there is no heating at all upstairs
adey, December 2012
pressure should read 1.5 bar sd

mm, December 2012
Quote "now there is no heating at all upstairs"
Bleeding radiators would not do that, It would if pressure dropped too much Stop any heating, NOT just upstairs. DO you have a pressure gauge, should read about 1 bar, for a combi boiler.
BUT
As you do not say what you have, just F30, difficult. I will assume ferroli f30, So you will have a filling loop somewhere close to the boiler, usually a flexible metal braided pipe, with a valve on. open the valve so pressure reads 1 bar, WHEN COLD.
Next time give full details, OR you might not get an answer