James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Charles asked ... Replace Belle switch?    |    Click here to ask your question

how do i add pressure on my f30 boiler?

I bled my upstairs radiators as they were only hot at the bottom. now there is no heating at all upstairs
adey, December 2012
pressure should read 1.5 bar sd

mm, December 2012
Quote "now there is no heating at all upstairs"
Bleeding radiators would not do that, It would if pressure dropped too much Stop any heating, NOT just upstairs. DO you have a pressure gauge, should read about 1 bar, for a combi boiler.
BUT
As you do not say what you have, just F30, difficult. I will assume ferroli f30, So you will have a filling loop somewhere close to the boiler, usually a flexible metal braided pipe, with a valve on. open the valve so pressure reads 1 bar, WHEN COLD.
Next time give full details, OR you might not get an answer

SD, December 2012
link Click here to see other fixes for F30.