3 hours ago Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

sime 90 gas boiler ?

boiler trys 2 fire up but all u hear is a clicking noise then after atleast 8 times doing this the pilot light does light
mike watts, March 2013
if u can see the blue spark it wont be the igniter. if it fires up and u can see the flame and it still keeps clicking then the flame electrode needs cleaning with sand paper. if there is the blue spark and no flame then the gas valve is on its way out. u may need to check the pcb if the gas valve requires changing to make sure the correct voltage is at the gas valve before changing the valve.

kash, March 2013