Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

how can fix my radiant rhr 29 b condense boiler?

one day last week my boiler wouldn't work hot water or heating then i took a look myself and the water in the loop where its got the pressure guage which is the operating pressure was at 0bar so i fill the loop up to 2bar then there was hot water and heating but after two days the water in the loop finished again the operating pressure was 0bar and i repeated the process can you tell me what is wrong?
hamid, November 2013
think 2 bar is to high.sit it around 1.1 bar when cold.then retry.If it still looses pressure you have a leak,faulty pressure release valve or expansion tank

A1, November 2013
fill system up to 1bar fire boiler up and watch pressure gauge,if pressure rises to 3 bar check previous questions about expansion vessel pressures,if not it could be the expansion relief valve that's faulty or you have a leak in the central heating system

toptrish, November 2013
link Click here to see other fixes for Radiant RHR 29 B.