Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    Click here to ask your question

How can I fix my vaillant combi boiler?

F22 flashing, don't know what tap to turn on
Martin, November 2013
http://www.youtube.com/watch?v=_Pf4qF6w68M

Q, December 2013
It's running dry fill waterto 1.2bar from filling loop right under boiler with radiator key it echo tec two white nob open and close if you are not sure refer to boiler manual,vent all radiators ,open big silver nut on pump let water out ,it may take 20 mits to clear air ,why water lost to be investigate it from pressure relief valve need new one

ltd, November 2013