GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Ferroli Optimax HE 31 - overflow pipe dripping F37?

We are having repeated F37 error with dropping pressure, having to top up at least twice a day. No leaks on rads but overflow from boiler outside dripping constantly. Would this cause the F37 problem
Neil, December 2013
Hi toptrish

Yes there is a pressure gauge, but it rarely goes up above 2.5 so that sounds like an expansion relief valve.

Neil, December 2013
Is there a pressure gauge? top up to 1 bar then fire boiler up, watch pressure gauge to see if it goes up to 3 bar if not and water is still dripping from overflow pipe the expansion relief valve needs replacing, If pressure goes up to 3 bar then the expansion tank requires attention

toptrish, December 2013