Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Click here to ask your question

Ferroli Optimax HE 31 - overflow pipe dripping F37?

We are having repeated F37 error with dropping pressure, having to top up at least twice a day. No leaks on rads but overflow from boiler outside dripping constantly. Would this cause the F37 problem
Neil, December 2013
Hi toptrish

Yes there is a pressure gauge, but it rarely goes up above 2.5 so that sounds like an expansion relief valve.

Neil, December 2013
Is there a pressure gauge? top up to 1 bar then fire boiler up, watch pressure gauge to see if it goes up to 3 bar if not and water is still dripping from overflow pipe the expansion relief valve needs replacing, If pressure goes up to 3 bar then the expansion tank requires attention

toptrish, December 2013