GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Why does my boiler keep switching on and off?

The boiler is a Main HE condensing. The problem only occurs when Hot Water Only is selected. If run from stone cold, it will run for a while and then off/on every few minutes but when hot water is selected with the tank already warm, the problem occurs. In summer it could take a day to heat up the water.
The system was power flushed and converted to have an expansion chamber but problem is still there
jimmo, May 2014
thanks very much - will run those checks

jimmo, May 2014
With the hot water tank cool/cold select hot water only and then monitor the flow and return pipes at the boiler,the flow pipe should gradually warm up and return should be cool,if the flow pipe gets quite hot quickly the water flow is too slow,
you say it was power flushed so the pump could be a factor.If the flow and return seem to heat up more or less together it could be the bypass valve that needs adjusting