Boiler pressure?

My boilers pressure is hitting 3 bar and now dripping out of pressure relief pipe, I have disconnected the filling loop but pressure is still rising
ZDave, October 2014
Take out water from Radiator air vent to 1.5 bar when boiler cold turn on boiler if still pressure is rising ,drain system and recharge expansion tank to as per boiler manual

ltd, October 2014