Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Guy asked ... Gaggenau fridge alarm problem?    |    Click here to ask your question

How do we get the LPG central heating boiler working again ?

Hi, our lpg tank ran empty so the central heating boiler stopped working

We have now had the tank re-filled but the boiler won't start and displays EA and RESET

We have pressed re-set many times but the boiler just runs for a minute or so and goes back to re-set

Presuming there is air in the lpg supply pipe is this a job only for a gas fitter ?
phil, January 2015
LPG systems need to be PRIMED & PURGED
espeacially when the tank has run dry
normally a task for a gas fitter
i would have thought the person refilling the LPG tank would have done that though

Q, February 2015