Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

my boiler over flow keeps dripping my boiler is a midas sfi comby?

my boiler over flow keeps dripping un till the low pressure light comes on and it cuts the boiler out . if i repressure the sistem it lights and runs well for short time . would this be the safty valve
stuart dyson, May 2016
When the boiler is cold set the pressure to 1 bar,fire boiler and let it get up to temperature, if the pressure reaches 3 bar the expansion vessel either needs recharging or replacing if it rises to 1.5-2 bar but the valve is dripping the valve needs changing

toptrish, May 2016
prv (pressure relief valve), first u need to find out what caused it to open. Was it due to overfilling the boiler with to much water, leaving the filling valve open or a fault on the boiler. If its a fault on the boiler u will need to rectify this first before replacing the valve otherwise it will just open again causing it to leak.