GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

danfoss SET3E contlolled heating system ?

In my Danfoss SET3E heating controlled system I can't turn the water heater section OFF! The switch on the controller is off and the light is extinguished but the boiler keeps going!. The only way to switch it off is to remove the 3 amp fuse. Switching on the 3 amp fuse and the boiler starts up again and the water gets very hot.
Alex, July 2016
We had a power cut when it came back on my danfoss set 3e didn't come back on

Mick, November 2021
My electric went out and when came back on again my danfoss set3e had not come back on I can't turn heat on there is no lights are timer working any ideas of to fix are do I intall new unit?

Barry, January 2017
Check the 2 switch wires are not mixed up ( in your programmer ) and it's always calling for heat instead of hot water . Possibly wired wrong ..

Michael ( electrician ), August 2016
OK, so: Is the controller telling the heating to run, when it shouldn't be telling it that, or is there a fault in the rest of the set up that means the heating runs?

There's a manual here:

http://www.gasapplianceguide.co.uk/Danfoss%20PDF/Danfoss%20SET%203E%20Install%20and%20User.pdf

You an check the switch with a battery and bulb or maybe a multimeter on ohms. Take the SET3 off the wall and check for a short between pins 4 and 5 on the back of the controller (see manual). If there's a short, get a new programmer.

The other possibility is if you have a diverter valve and it is stuck in "Heating" position. With that kind of set up, the controller calls for heating but that only makes the diverter valve run. When the diverter valve is in the right position it turns the boiler and / or pump on. If the valve is stuck in "Heat" the boiler will run all the time.

You 'll need to find it and check. There's usually a manual lever you can twiddle. There's some generic info here:

http://danfoss-randall.co.uk/PCMPDF/Introducing%20Motorised%20Valves%20Part%204.pdf

If you know what make/model yours is, you should be able to find info online. (It may be an integral part of the boiler)

XXX, July 2016