Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    alex asked ... Reanult clio 2008?    |    Click here to ask your question

Can I use a Scantronic 9448+ panel without door contacts ?

I have replaced my old security system panel with a new Scantronic 9448+ model.. Originally did not have Door contacts as the original installation only used PIRs.. Installing and programming the 9448, I don't seem to be able to enter the bldg. without triggering an instant alarm and not having the entry time delay. Is this due to not having door contacts?
If so can this be worked around or do I have to install the door contacts for it to work as required?
Steve, June 2017
the dedicated zone is marked EE on the pcb entry /exit wire the pir to this and your troubles are over

gts, June 2017
you can use a pir to trip the timing circuit just wire it to the dedicated circuit for the door contact

gts, June 2017
...... sorry, you will then be able to have an entry/exit delay installed in a sensible manor

magpye, June 2017
Install a door contact at your entry/exit door, that is always the correct way to do it

magpye, June 2017