how to set veritas 8c alarm?

i have reset the engineers code, when i exit the system works great, when i return the system goes into full alarm and the only way i can reset is to put in the engineers code. please help
rob, January 2007


done
i cannot get the door sensor to work entry/exit and dont have any instruction manule can you help me

dmcevoy, April 2012
Try Alarmhelp.net for an engineers manual.

Alarm man, February 2007
Hi Rob/Imran
it seems that you both may have the same problem here. I think that you may have the entry exit door set for guard instead of entry/exit.
I assume that your entry is your front doors and are set as zone 1.
To set them for entry exit.
1/ enter the engineers code [4 digits]
2/ enter 0.0. all the zone lights will illuminate.
3/ enter 1.1. [after the second '1' the current zone setting will illuminate. eg if no 3 lights this means that the zone is set to guard no 6 means it is set for entry exit]
4/ press 6. then PROG, the system will chime and revert back to the programming menu. this should have now set your door to entry exit .
5/ if you enter '1' instead of '6' this should set for entry exit with final door set. this means that the alarm will set 5 seconds after the door is shut. irrespective of the time delay that is already entered. and the strobe will flash 5 times to indicate alarm set.
I can probably photocopy the installation manual and send a copy if required. my email is john@ajtnet.com

John, February 2007
why change the engineers code?
Have you reset back to default settings?

Try default code 4321

John, January 2007
Hi, I've got the same issue. I'm looking for an engineers manual on the net. for the time being I have to omit the door sensor so that when I return the alarm doesnt come on, but at least the rest of the house is still protected.

Imran, January 2007