Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Combi BOILER is not worming up hot?

Vokera Excell 80SP CombI Boiler works okay but fire up for about 15 min. then shuts off about 3 min, therfore the radiators does not worm up to the high level, aldough the thermostat is on Max.
Hot water is fine.
Any help would appreciated.
Vaz, January 2007
Boilers regulate water flow temperature, and when the chosen setting is reached they will switch off and after some time will come back on again dependinging on the temperature of the return flow, so either increase the flow temperature and also check that all your rads are fully bleeded or vented i.e. no air trapped in them, and then also ensure that there is no flow restriction in the rad valves, a faulty diverter valev can cause similar symtoms but I wouldn't have thought this would be the case in your situation as you said it comes on for almost 15 minutes, a faulty diverter valve will shut the heatinmg down very rapidly withing a few seconds.

Mike, March 2007