Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Marc Nollid asked ... Nissan Micra mk 5 2018 rear seat mecanism?    |    Maggie asked ... New Home 535?    |    Click here to ask your question

can anyone?

can anyone tell me why when my heating is on the boiler pressure keeps rising from 1Bar all the way up past 2bar at this point i switch it off because it might blow if it rises any more
j helliwell, June 2007
assuming that the pressure vessel is ok

you are going from one to two bar because of water expansion when heated.

I would only expect 1 to 1.5 bar

it could be you have a lot of radiators or the vessel needs replacing or re-charging.
At 3 bar the pressure relief valve will operate and excess water will be shot out through the wall. This is not dangerous but not desirable.

dave broadbent, June 2007