marc asked ... La machine 1 type 813?    |    Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    Click here to ask your question

The pressure has dropped significantly below 1 on my Worcester 9.24 boiler?

I'm having problems with my Worcester 9.24 Boiler where although we have hot water it is only for a short time. Hot water only works when the heating is on too. I think it is the pressure as it has dropped below 1! - How can i increase the pressure? Or is it something more serious?
Mike Carter, July 2007
On a bosch worcester boiler, there is a water make-up tap fitted usually just below the boiler to allow the sealed radiator part of the system to be topped up or pressurised with water. However I recommend that you check your system for any leaks first. If you are sure that you dont have any leaks, then by opening the make-up valve you can top the system up until the pressure dial reads 1.5bar. At this point, close the make-up valve as too high a pressure will damage the system. You wil then need to go around all the radiators and bleed them one-by-one to expel any air. Re-check the system pressure and if necassary, open the make-up valve to restore the pressure, but do make sure that once it is at 1.5bar, you close the make-up valve. Good luck.

Chris B, July 2007