3 hours ago Andrew asked ... Jcb cordless 20v combi drill?    |    marc asked ... La machine 1 type 813?    |    Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Click here to ask your question

worcester 28 cdi c/h pressure prob?

hi i have a 28 cdi worcester combi. on the c/h side ...pressuer build-up after 10 min or so .rises from 1 bar to 3+ bar then of course pressure valve lets out side.
any help with this expansion problem? thanks...
alex., August 2007
thanks was low pressure in vessel,,, so far holding at 1 bar
thanks again///

alex, August 2007
pressure at o bar after heating is off . re fill to 1 bar heating back on then pressure up to ,3+ bar the valve lets again back to 0 bar ????

alex, August 2007
if pressure go's back down when heating is off then your expanssion vessel is low on pressure or is split.

hi-spec plumbing, August 2007