Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

Vokera Linear 24 timer fault?

The boiler works fine in both hot water and central heating modes until the timer is set. When the time is reached for the heating to start everything runs as normal until the selected temperature is achieved and the flames goes out. When the boiler tries to re-light the flame lights increases to max and then just go out. The boiler repeatedly does this until fault code 03 appears and from this point nothing happens. I've had heat exchangers replaced due to over pressuring problems, thermisters, gas valve, flame sensors, 3x PCB's and the selector dials at the front due to constant problems. I'm a little lost at what to do now, can anybody help?
Jon, September 2007
I've finally had a chance to have a look into the boiler now and i've found the microswitch on the flue pressure differential switch to be the fault. A new one has been ordered from ebay for £20, so hopefully a cheap fix. Thanks for a steer in the right direction Alan.

Jon, October 2007
i think this could be a problem with the air sensing tubes or the venturis being blocked, i dont think it has any connection to your timer, if it tends to run ok with the combustion cover off then i would look at the tubes and venturis

alan, September 2007