Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

REPRESSURING BOILER?

I AM CONSTANTLY REPRESSURISING MY VOKERA LINEA 24 BOILER.CAN ANYONE EXPLAIN WHY I HAVE TO KEEP DOING THIS.
GORDON, September 2007
Its leaking?. Does the pressure go right up to 3 bar or so when the central heating heats up?, if so your expansion vessel needs recharging, a possible DIY job. With zero system pressure pump up the expansion vessel to 12 or 15 psi, depending on your manual. Try searching for expansion vessel on this site or googling.

c, September 2007
link Click here to see other fixes for Vokera.