Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Pressure rising each time boiler used?

Have Glow-worm Combi 30ci plus. Had the (cracked) expansion vessel replaced after leaking. Boiler pressure now rises from 1 bar to about 2.5 bar each time heating/hot water used. Have to release pressure using valve (into a bowl under boiler, very messy) Won't go down of own accord. Is it the heat exchanger that's faulty? How much to replace/fix?
Peter McGowan, October 2007
the expansion vessel is split in two inside with a diaphram! it is pressurised on the dr side with air to balance the pressure in the sealed hot water system, if it is not filled with air you will get that problem, also the boiler will automatically discharge the pressure out the pressure release at 3 bar!

toby, April 2008