2 hours ago Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Nick asked ... Oven spark Continuing after lit?    |    Andrew asked ... Jcb cordless 20v combi drill?    |    marc asked ... La machine 1 type 813?    |    Click here to ask your question

what is wrong vaillant 242E,282E?

when i first run the hot water tap i get hot water for 30 seconds then goes cold same happens when i put the heating on
melvin clarke, October 2007
take off front cover to reveal burner ass`y. Bottom l/hand side is ntc sensor, follow wire back to where it attatches to dhw sensor (black one) and disconnect it but dont let it touch boiler. replace front cover and try htg , if it works then thats ur fault. these can be swapped without draining boiler but dont run boiler without the sensor being connected as what i`m telling u to do is only 4 test purposes.

paul, October 2007
either boiler blocked on htg pipework in boiler or flow and return sensors faulty

paul martin, October 2007