GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

how can i fix my worcester28cdi combi central heating?

pressure is set at 1 bar when cold filling loop valve is closed and filling key is removed but when central heating is run pressure goes up to 3 1/2 bar and water comes out of release valve overflow pipe.When central heating pressure is reduced again back down to 1bar and run again pressure rises again the same.
mr Parry, October 2007
hot water is ok but no heating

steve, October 2011
Get a replacement expansion vessell the diaphragm is perforated provided that the check valve on the internal filling loop isn't passing water.

shaz the gas fitter, October 2007
It sounds like your expansion vessel has gone, they are a bit of a pig to replace with original part. If you have room you can fit a remote expansion vessel onto the return pipework, a 12lt vessel should cost no more than forty pounds.

colin, October 2007
if pressure rises(over a couple of hours) with no heating then the plate heat exchanger is passing. if pressure rises fairly quickly with heating then drain system, press shreider valve in red expansion vessel, if water comes out then vessel gone, if nothing then use a car foot pump and pressurise to just under 1bar refill system and happy days

waynethegas, October 2007