GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

How can i fix my Ariston Combi Boiler?

The water will only heat up when the heating is on?
The shower will fluctuate from hot to cold whilst the heating is on?
I cannot get the water to heat without the heating on?
The pressure does not hold during the day/night, the pressure drops and the water overflows.

Can someone help.
Geoff, April 2005
hi geoff the problem you have is with the diverter valve it will either be internally coated with sludge from the heating system resulting in the radiators getting warm when you are using hot water only or the water valve diaphragm has sptit . the water leaving the overflow will be due to a worn safety valve or too much pressure being put into the boiler by you via the filling valva assy or the boilers expansion vessel has lost its charge pressure resulting in the boilers internal pressure rising to above 3 bar gauge pressure after the boiler has been on for approx half an hour. the boilers safety valve is set to release water to outside at approx 3 bar and is preset by the manufacturers hope this helps

joe waldron, April 2005
link Click here to see other fixes for Ariston.