GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

ferroli optima 700 water pressure problems?

hi the water pressure on the boiler is reading below 1 bar when its topped up to above that and the heatings on it drips water from the overflow outside. once the heating is turned off and cooled down the pressure guage reads under the min 1 bar any suggestions please ?
wayne, November 2007
problem now solved -replaced the pressure relief valve

thanks

wayne, November 2007
thanks mr a
yes it does go to nearly 3 bar then drops to almost 0 is the repressurising very expensive ? (dont suppose its a diy job)

thanks agian

wayne, November 2007
Does the pressure raise up to around 3bar when heating on? If so, the expansion vessel will requires repressurising. If this doesnt happen and it just contantly drips you can either remove and clean the pressure relief valve or replace the valve.

Mr A, November 2007