GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

vaillant 242 help!?

boiler starts sequence fan runs then goes to lockout,no spark at electrode,no gas getting through,have cleaned all tubes,checked all reset switches,have linked pressure switch out and fitted new pcb and transformer but still the same.could anyone please help
dave m, November 2007
best of luck

gedodonnell, March 2010
if you link the APS out to early in the cycle the boiler pcb will detect it as a fault and go to lock out...Try shorting the APS secounds after the fan begins to run ......this will cause the boiler to go into ignition ..best of luck

gedodonnell, November 2007