andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

vaillant 242 help!?

boiler starts sequence fan runs then goes to lockout,no spark at electrode,no gas getting through,have cleaned all tubes,checked all reset switches,have linked pressure switch out and fitted new pcb and transformer but still the same.could anyone please help
dave m, November 2007
best of luck

gedodonnell, March 2010
if you link the APS out to early in the cycle the boiler pcb will detect it as a fault and go to lock out...Try shorting the APS secounds after the fan begins to run ......this will cause the boiler to go into ignition ..best of luck

gedodonnell, November 2007