3 hours ago Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

Solenoid vale not opening?

Trianco/Monoflame Minor/Danfoss pump(new)
Pump changed due to fault, now the solenoid valve remains closed not allowing fuel to flow ! Lock-out does not "lock-out" but ignitor and fan work OK. HELP !!!
Mark Golledge, December 2007
Hi Mark
Have the solenoid valve coil checked and prove there is a signal getting to it from the control box. Also check that the pump has been vented and fully primed. Has the operating oil pressure been set correctly on the new pump.

D.R., January 2008