andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Combi boiler Baxi 105e instant?

Hi,
I have a 2 year old Baxi 105e instant combi boiler, recently within the last month I have noticed the boiler losing too much pressure [I have replaced the pressure valve but this has not solved the problem] The pressure guage on the front panel keeps dropping to the zero mark I am constantly charging the system with more water. Also I have noticed too much water draining through the external overflo pipe. Can anyone please help?
Wishing you a Happy & Prosperous New Year
Adam
adam sultan, December 2007
you need a new expansion vessel

paul samuels, December 2007