Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

Vokera linea 24 boiler will not fill?

Hi! my friends vokera linea 24 boiler pressure has dropped i tried to fill it using the relevant tap which i have done many times before but this time the pressure gauge isn't rising, does this mean the inlet cock is faulty, any idea.

regards
wayne
Wayne, December 2007
You can't here any wateer entering the system and when i tried disconecting the filling loop to check if its blocked water is coming back out of the system so this make me think the inlet valve is faulty.

Wayne, December 2007
When you operate the filling valve can you hear water entering the boiler. If this is the case check the outside drain cock is not open and the pressure relief valve is not passing water to outside. Is there water passing through the boiler to the hot water taps. If there is your diagnosis may be correct however the on line filter may be blocked which is located directly downstream of the filling valve.

Donald J. Ross, December 2007