Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Nick asked ... Oven spark Continuing after lit?    |    Click here to ask your question

Un Vented Santon Premier Plus PP210E Thermal Cut Out Keeps Tripping Out?

I have a Santon Premier Plus PP210E un vented hot water cylinder in a flat that is only heated by electric. It Has 2 immersion heaters, top and a lower one. The lower one's Thermal cut out has tripped twice in 3 weeks. The immersion heater can be set to a maximum of 70 degrees and the thermal cut out should operate at 80 - 85 degrees. I am sure one of these must be faulty if it keeps tripping. I think it could be the combined thermostat & thermal cut out device the pushes on to the immersion heaters terminals but i could be wrong as the device takes its info from the immersion heater element. Any advice and help would be greatfully recieved.
Phil greenwood, January 2008
Your thermostat is likely burnt out - get down and have a look at the wiring connections to the thermostat - you'll likely see signs of scorching. (BE SURE TO DISCONNECT FROM MAINS BEFORE GOING ANYWHERE NEAR IT). If it's scorched 90% likely dead - remove and replace it (and re-wire as the wiring loom is also now likely to be burnt solid!)

Si, April 2010
I have excatly the same issue with mine.

Did you sort this one out? Would be grateful to know if so, and what the problem was.