Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

what is wrong with my baxi 105e instant?

Both c/h and dhw keep tripping off after a certain period of time. I have replaced overheat thermostat as an initial measure but the problem will not go away. the heater fires up when the system cools down but the amount of available hot water is variable sometimes only a couple of minutes. grateful for any assistance. Jim.
jim Rothwell, January 2008
Hello, There is a possibility that your boiler heat exchanger is sludged up with either limescale or rust from the radiators.
This would slow the flow down through the heat exchanger causing the boiler to overheat.
A quick repair would be to add a flushing agent to your system like fernox. This would only cure your rust (ferrous oxide) problem.
If the cause is down to limescale the heat exchanger would have to be powerflushed. Quite an expensive job.
Regards,
Nick

Nick Frost, January 2008