Freya asked ... Frister & Rossman Cub7 Sewing Machine?    |    katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Click here to ask your question

do i need just a new valve?

water is coming out of theautomatic air release valve have been running boiler at 2bar do i need a new air valve it is a biasi 24s thanks
mr m bott, January 2008
Yes you do need a new auto air vent. Look for the appliance 7 digit Gas Council no (GC no) and take that along with make and model of appliance to a heating spares shop and they should be able to provide you with one there and then. Most AAV's are always in stock and usually cost around £10 - £20.

Curtis Patrick, February 2008
should only be running at 1 bar , try that , if it still leaks get new valve, - make sure its not slack

ian, February 2008