Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    Click here to ask your question

Weil-McLain Gas Fired Boiler?

Boiler is located in the basement. 1st floor radiators have water coming out when manually vented. Some 2nd floor radiators water coming out when manually vented, others vent some air then nothing. Should water becoming out when air has been venting. What would be causing the radiators to have some heat but no water or air out of the manual vent?
EC com., February 2008
if you have got a sealed system,no tank in the loft,then you have to put water in yourself through a filling loop until a pressure gauge shows 1.5 bar. this filling loop looks like a braided hose with a tap at one or both ends . turn on untill pressure reads 2 turn off then bleed highest rads if air stops coming out without water , then top up again to 1.5 bar.

combiking, March 2008