4 hours ago Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

How to Adjust the pressure after bleeding a radiator?

I'm decorating and need to remove a radiator. When i put it back i will have to re pressurise the system but the manual does not show how to do this. I know it will just be one of the taps but which one?
Baxi 105e
Sean Patterson, March 2008
Baxi 105 will have a 'filling loop' under the boiler. It connects the mains water to enter the central heating water.

Open the valves on each side of this loop and you will hear the water entering. WATCH the pressure rise on the meter under the flap at the boiler bottom!! Raise this pressure to 1 - 1.5 Bar, & close the valves. It may need more than one go to replace a radiator.

Steve, March 2008