Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

How to Adjust the pressure after bleeding a radiator?

I'm decorating and need to remove a radiator. When i put it back i will have to re pressurise the system but the manual does not show how to do this. I know it will just be one of the taps but which one?
Baxi 105e
Sean Patterson, March 2008
Baxi 105 will have a 'filling loop' under the boiler. It connects the mains water to enter the central heating water.

Open the valves on each side of this loop and you will hear the water entering. WATCH the pressure rise on the meter under the flap at the boiler bottom!! Raise this pressure to 1 - 1.5 Bar, & close the valves. It may need more than one go to replace a radiator.

Steve, March 2008