GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Potterton combi 80 boiler?

I have re pressurised the expansion tank as suggested. There is no water coming from the valve on the unit nor any wetness around the rim. The problem stays the same with the bar guage rising to the red section when the heating is hot and slowly falling to zero red area when cold so I have to top up the water or the pump makes a growling sound on turning on the system. Have been told it may be a pressure leak in the pipe work so have put leak seal into the system still no changes so stumped, please help if possible.
johnyonenote, March 2008
It sounds like either the expansion vessel diaphragm has gone, do you get water from the air valve on the expansion vessel, or the pipework leading to the expansion vessel is blocked.

gary.wright53@googlemail.com, March 2008
link Click here to see other fixes for Potterton.