Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

how can i find out if my potterton ep2001 programmer is u/s?

I belive my potterton ep2001 programmer is nackered as it will only put the central heating on twice a day no matter what selection i have i.e constant. I do have a thermostat switch which in the past has allowed me to have the programer on constant and i have been able to control the heating from that However it now has no effect and the potterton seems to be stuck on a preset auto setting. Is there anyway i can test the programer to see if it is that or my thermostat switch(british gas PT5) which is at fault
John Leadley, March 2008
if the heating is on at the clock [ the red light is on ] the heating should come on and off with the use of the room thermostat as that takes priority....... if u are having probs with the clock hold down the + and - buttons together for 10 seconds this will reset the clock back to the factory settings

matt the boiler man, March 2008