Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    Click here to ask your question

How can I fix my CHAFFOTEAUX MAURY BRITONY COMBI SE?

The self diagnostic lights 70 and 80 are flashing. I have tried the reset button. I have cheched the water gauge ok. I do not have a manual. Please help
Peter, April 2008
Graham thanx for your message. I clean it and my fault is gone off. :)

sahin, January 2014
what does error code e02 mean

paul smith, March 2013
my chaffoteaux boiler keeps tripping out

sherrie harrison, July 2011
i have the 60 flashing which is the ironisation circuit board. does anyone know where i can get one from

NIK, December 2010
my rads dont seem to get red hot, they only ever get warm?

danny, January 2010
Not sure if you are still looking for help on this, but here goes anyway.

Firstly, you can download manuals for this boiler from the C&M website -

www.chaffoteaux.co.uk

If you download the Installation and Operating Instructions manual, it has a table of the fault codes on page 15. Also found on page 10 of the Maintenance and Service guide.

In your case, 70 & 80 flashing means no flame detection.
I would assume this is referring to ionization electrode, which detects that the burner is lit. Try cleaning it (it's metal and can become oxidised). Otherwise, try replacing it.

I have fault 40+60+80, which appears to be a common fault with these boilers. This seems to relate to a faulty relay on the pcb, which drives the flue fan.
Replacement pcb is over £130, so I am attempting to replace the relay myself, though struggling to find a supplier of the correct type of relay.
Which, by the way, is what brought me here today!

Graham, September 2008