andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Ravenheat csi 85?

Hi,my Ravenheat Csi 85 fires up 2/3 times a minute in CH mode.The heating works fine but obviously somethings amiss.
Davd Smith, April 2008
Firstly, remove all external controls, to prove the problem is with the boile rand not the valves/stats.

Make sure your system pressure is between 1-1.5 bar, if not refill and vent all air.
If problem persists, ensure pump is running, check ch thermisters.

T, April 2008