Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

how to stop a pin hole leak in a water jacket of a 5 year old boiler?

when the system calls for hot water, the boiler kicks on and it starts spraying hot water from one of the sections. it is a small single house Burnham hotwater boiler.
Homer Jennings, April 2008
my first recommendation would be to double check your warranty as most cast iron boilers should be good for for at least 5 years. If the water is spraying from a joint between the cast iron sections, you may try to tighten the draw bolts that hold the sections together. if the leak is within a section, you may be able to weld the leak if it is a pinhole or else replace the section.

roscoe, June 2008
time to get a technician out luv