Dwayne B. asked ... Intermittent (twice) Then Complete Loss of Power?    |    Aunt Bee asked ... Bernina Update 1630 work light not working?    |    Larry asked ... Hybrid Weed wacker not working with battery?    |    Dan asked ... Why is Google Keep so slow on my iPhone?    |    dave s asked ... Transmission not working?    |    Click here to ask your question

My Potterton Puma 80 has pressure build up problem!?

When the boiler is providing hot water only everything is fine, operating without any problem. But when the central heating is turned on, the radiators get hot and the water is circulating, and, but the boiler pressure goes up from 1 1/2 bar to 4, it just keeps increasing! Thus intern releasing the pressure relief valve set at 3 bar, and then when everything cools down, the low pressure light comes on. The boiler gets topped up and the whole circle starts again. Any ideas as to what might be causing this???
Angela, May 2008
Thanks Iain for your quick reply.
Is the expansion vessel the little round ball with the car type valve on the top, or is it the big orange tank right at the back of the boiler?

Angela, May 2008
expansion vessel needs recharging or replacing. my bets would be 99% on replacing

iain, May 2008