GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

My Potterton Puma 80 has pressure build up problem!?

When the boiler is providing hot water only everything is fine, operating without any problem. But when the central heating is turned on, the radiators get hot and the water is circulating, and, but the boiler pressure goes up from 1 1/2 bar to 4, it just keeps increasing! Thus intern releasing the pressure relief valve set at 3 bar, and then when everything cools down, the low pressure light comes on. The boiler gets topped up and the whole circle starts again. Any ideas as to what might be causing this???
Angela, May 2008
Thanks Iain for your quick reply.
Is the expansion vessel the little round ball with the car type valve on the top, or is it the big orange tank right at the back of the boiler?

Angela, May 2008
expansion vessel needs recharging or replacing. my bets would be 99% on replacing

iain, May 2008
link Click here to see other fixes for Potterton.