Jon asked ... How do I remove the flywheel. Mountfield 1640h ride on mower?    |    Keith Mumby asked ... Fordson starter solenoid?    |    Suzanne asked ... Washing programme stops after 3 minutes?    |    Rif asked ... Kenwood Dishwasher KID60S20 leaking from front?    |    Fraser asked ... Spares for power craft ppcs 38cc?    |    Click here to ask your question

My Potterton Puma 80 has pressure build up problem!?

When the boiler is providing hot water only everything is fine, operating without any problem. But when the central heating is turned on, the radiators get hot and the water is circulating, and, but the boiler pressure goes up from 1 1/2 bar to 4, it just keeps increasing! Thus intern releasing the pressure relief valve set at 3 bar, and then when everything cools down, the low pressure light comes on. The boiler gets topped up and the whole circle starts again. Any ideas as to what might be causing this???
Angela, May 2008
Thanks Iain for your quick reply.
Is the expansion vessel the little round ball with the car type valve on the top, or is it the big orange tank right at the back of the boiler?

Angela, May 2008
expansion vessel needs recharging or replacing. my bets would be 99% on replacing

iain, May 2008